TECHNICAL SPECIFICATIONS
|
|
|
MODEL
I.D.
|
CV2
|
| VOLTAGE & PHASE |
208Y/120V
3 PHASE,4WIRE |
| SIZE |
2.75X4.0X2.5 INCHES |
| APPROXIMATE WEIGHT |
4.0 LBS. |
| NEUTRAL COLOR |
WHITE |
| L1 COLOUR & VOLTS |
ORANGE/120V |
| L2 COLOUR & VOLTS |
ORANGE/120V |
| L3 COLOUR & VOLTS |
ORANGE/120VOLTS |
| L1-L2 VOLTS |
208V |
| L2-L3 VOLTS |
208V |
| L1-L3 VOLTS |
208V |
| GROUND COLOUR |
GREEN |
WIRE SIZE/INSULATION
NEUTRAL/PHASE |
# 12 THHN |
| GROUND INSULATION |
# 12 T-90 |
| CASE VOLTAGE WITHSTAND |
10,OOO VOLTS |
MAXIMUM TOTAL
ENERGY RATING
PHASE TO PHASE TO NEUTRAL/GR |
> 3000 JOULES |
MAXIMUM TOTAL
ENERGY RATING
PHASE TO PHASE TO NEUTRAL/GR |
>10,000 JOULES |
RESPONSE TIME NANO-SECONDS
6 INCH LEAD |
< 1.0 N SEC |
RESPONSE TIME NANO-SECONDS
18 INCH LEAD |
< 2.0 N SEC |
POWER LINE STIKE:
MAXIMUM DISTANCE
DOWN LINE FROM
SUPPRESSOR TO INSURE
100%
EQUIPMENT SURVIVAL |
18"/W 6" LEAD
30"/W 18" LEAD
|
DISCHARGE CAPACITY
1 PHASE
TO NEUTRAL GROUND
8 X 20 MICRO SECOND
PULSE |
20,800 |
UL
LISTED: EXCEEDS ANSE/IEEE
C62.1
STANDARD
|
ULTIMATE
SPIKE/SURGE
PROTECTION
|
|
CV2
|
| DESIGNATED
LEG |
120 |
208 |
| CLAMP
VOLTAGE |
130 |
230 |
UNITS MUST BE INSTALLED BY A QUALIFIED ELECTRICIAN
AND
PROPER ELECTRICAL SAFETY AUTHORITY PERMITS IN PLACE
| MODEL
I.D. |
CV3 |
CV5 |
| VOLTAGE
& PHASE |
480Y/277V
3Ø,
3W
WYE |
240/120V
Tapped
Delta
3Ø,
4W |
| SIZE |
3.0X4.5X4.75
INCHES |
3.0X4.5X4.75
INCHES |
| APPROXIMATE
WIEGHT |
10
LBS. |
10
LBS. |
NEUTRAL
COLOR
(REFERENCE) |
WHITE |
WHITE |
L1
TO NEUTRAL VOLTS
(COLOR) |
BLU/277V |
BLU/120V |
L2
TO NEUTRAL VOLTS
(COLOR) |
BLU/277V |
BLU/120V |
L3
TO NEUTRAL VOLTS
(COLOR) |
BLU/277V |
BLU/120V |
| L3-L2-L1
VOLTS |
480
VOLTS |
240
VOLTS |
| GROUND
COLOUR |
GREEN |
GREEN |
WIRE
SIZE/INSULATION
NEUTRAL/PHASE |
#
10 THHN |
#
10 THHN |
| CASE
VOLTAGE WITHSTAND |
10,000
VOLTS |
10,000
VOLTS |
| MAXIMUM
TOTAL ENERGY RATING PHASE TO NEUTRAL/GR |
5,000
JOULES |
5,000
JOULES |
MAXIMUM
TOTAL ENERGY RATING
PHASE
TO PHASE TO NEUTRAL/GR |
5,000
JOULES |
5,000
JOULES |
RESPONSE
TIME NANO-SECONDS
6
INCH LEAD |
1.0
N SEC |
1.0
N SEC |
RESPONSE
TIME NANO-SECONDS
18
INCH LEAD |
2.0
N SEC |
2.0
N SEC |
POWER
LINE STRIKE:
MAXIMUM
DISTANCE
6” LEADS |
18" |
18" |
DOWNLINE
FROM
SUPPRESSOR
TO
18” LEADS INSURE
100%
EQUIPMENT SURVIVAL. |
30" |
30" |
DISCHARGE
CAPACITY 1 PHASE TO NEUTRAL/GROUND
8 X
20 MICRO SECOND PULSE |
30,000
AMPS |
30,000
AMPS |
DESIGNATED
LEG
|
CLAMP
VOLTAGE
|
DESIGNATED
LEG
|
CLAMP
VOLTAGE
|
DESIGNATED
LEG
|
CLAMP
VOLTAGE
|
|
277
|
320
|
480
|
510
|
240
|
275
|
UNITS MUST BE
INSTALLED BY A QUALIFIED ELECTRICIAN AND PROPER ELECTRICAL
SAFETY AUTHORITY PERMITS IN PLACE.
|
|
service@mimcv.com
|